Presscon vacuum and overpressure safety valve
The Presscon PV-Series vacuum overpressure protectors provide protection for your vertical buffer tank from overpressure and vacuum.
The vacuum overpressure protector is placed on the roof of the vertical buffer tank. This enables the vacuum overpressure protector to protect the vertical buffer tank against vacuum and overpressure.
How does the Presscon Vacuum overpressure protector work?
If the pressure of the nitrogen above the water increases due to refilling, expansion and/or steam generation, the working pressure valve opens. If it cannot handle it, the maximum pressure side of the vacuum pressure relief valve opens. An open connection to the outside air is created. Excess nitrogen can flow out through the opening. The working pressure valve remains open until the pressure equals the working pressure. If the pressure continues to rise, the pressure relief valve also opens when the maximum excess pressure is reached. The vacuum overpressure safety valve remains open until the pressure drops below the maximum overpressure. The moment the pressure drops and a vacuum occurs, the vacuum valve allows air into the tank. This is to prevent negative pressure from forming, causing the tank to implode.
Three models are available. See attached pdf for more technical information.
|
|
|
|
Type |
PV 80/25/20-2 |
PV 150/25/20-2 |
PV 200/25/20-2 |
Volume of vertical buffer tank
|
up to 999 m³ |
1,000 m³ to 2,499 m³ |
> 2,500 m³ |
Flange size
|
DN 80 PN6 ND6 |
DN 150 PN6 ND6 |
DN 200 PN6 ND6 |
Opening pressure relief valve
|
25 mbar |
25 mbar |
25 mbar |
Opening pressure of working pressure valve
|
20 mbar |
20 mbar |
20 mbar |
Opening pressure vacuum valve |
-2 mbar |
-2 mbar |
-2 mbar |
Weight
|
14 kg |
24 kg |
48 kg |
Dimensions |
43x22x35 cm |
53x30x38 cm |
67x37x40 cm
|
At additional cost, valves that are protected against frost are available.
The Presscon vacuum overpressure protector is provided with a heating ribbon and an insulating jacket. The heating ribbon is 24V controlled and switches at 3˚C.
Presscon vacuum and overpressure safety valve